Plc 3 block transfer timing, 8ć14 – Rockwell Automation 1771-QC , D17716.5.25 SER/B SERVO POS User Manual

Page 175

Advertising
background image

Chapter 8

8Ć14

Figure 8.5

BlockĆtransfer Instructions for PLCĆ3 Controllers

EN

BTR
BLOCK XFER READ
RACK:
GROUP:
MODULE:
DATA:

001

1

1 = HIGH

FI001:0005

DN

LENGTH:

0

CNTL:

FB001:0000

ER

CNTL

12
CNTL

15
CNTL

13

EN

BLOCK XFER WRITE
RACK:
GROUP:
MODULE:
DATA:

001

1

1 = HIGH

FO001:0004

DN

LENGTH:

0

CNTL:

FB001:0000

ER

CNTL

02
CNTL

05
CNTL

03

Block transfer instructions use two files when transferring data and
commands between the block transfer module and the PLC-3 processor:

a data file that contains data being transferred
a control file that contains control bits, module location, data table

address and length of the data file

The I/O scanner directs communication between the block-transfer
module and processor. Once the block-transfer instruction is enabled, the
scanner directs the transfer of data to or from the enabled block transfer
module according to the information contained in the instruction’s control
file. Once the instruction is enabled, the PLC-3 processor automatically
sets and resets the control bits in accordance with the various steps
required to execute the read or write operation.

The execution time required to complete a read/write block transfer
depends on factors that include the number of:

words of user program
active I/O channels on the scanner
I/O chassis entries on the I/O chassis scanning sequence list for the

channel

PLCĆ3 Block Transfer Timing