10 - troubleshooting, Chapter objectives, Monitoring 1771 m3 controller indicators – Rockwell Automation 1771-QC , D17716.5.25 SER/B SERVO POS User Manual

Page 213: 10ć1, Troubleshooting

Advertising
background image

Chapter

10

10Ć1

Troubleshooting

This chapter describes the LED indicators on the 1771-M3 controller and
1771-ES expander modules. It also presents a troubleshooting flowchart.
The flowchart provides a logical sequence for evaluating servo
positioning assembly condition. Used in conjunction with the indicators
and the status block, it can help you detect problems in servo positioning
assembly operation.

The status block provides continually updated information about axis and
servo positioning assembly conditions. Refer to chapter 7, section titled
“Status Block” (p. 7-4) for a detailed description of the status block.

The servo controller module has three indicators (Figure 10.1):

Figure 10.1

1771ĆM3 Controller Indicators

SERVO

CONTROLLER

Processor Communication

Fault (Red)

Expander Communication

Fault (Red)

Active (Green)

Processor communication fault (PROC COMM FAULT) - This red

indicator is normally off. It turns on to indicate a communication fault
between the PC processor and the 1771-M3 controller. Such a font
could be caused by hardware, or by a data block overlapping a

Chapter Objectives

Monitoring 1771ĆM3 Controller

Indicators