Formatting and Interpreting Data Blocks

Chapter 7

7Ć11

Figure 7.5

Second Status Word

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Second Status word

11054

Command Taken

Diagnostic Valid

Position Valid

Following

Error Valid

Axis Fault

Move Number;

BCD Format

Loss of Power

Programming Error

Block ID

Word 4 (Axis 1)

Word 8 (Axis 2)

Word 12 (Axis 3)

Bit 0Ć5 Move Number

These bits indicate the active move within the moveset in BCD format.

Bit 6 Loss of Power

When set, this bit indicates a loss of power across one of the following
sets of terminals:

terminals 1 and 12 (input supply) of the left wiring arm
terminals 1 and 6 (analog supply) of the right wiring arm

If this bit is on, then the immediate stop bit in the status block is on,
indicating that immediate stop has been executed after detection of the
loss of power.

Bit 7 Programming Error

If the 1771-M3 controller detects an illegal bit combination, such as a
non-BCD value where one is expected, or an illegal bit combination in the
command block, it turns on the programming error bit.

When this bit is on, bits 10 thru 12 of this status word provide a code to
identify the block containing the programming error.