Troubleshooting chapter 10 – Rockwell Automation 1771-QC , D17716.5.25 SER/B SERVO POS User Manual

Page 220

Advertising
background image

Troubleshooting

Chapter 10

10Ć8

Figure 10.5

Troubleshooting Flowchart

START

Processor

RUN

indicator

?

I/O

adapter ACTIVE

indicator

?

PC

communications

fault

indicator

Expander

communication

fault indicator

?

Processor

RUN

indicator

?

1771-M3

controller

ACTIVE indicator

on constant

1771-ES

expander

ACTIVE indicator

on?

1771-ES

Expander

Diagnostic indicator

on ?

?

?

Consult Assembly

and Installation

PC Manual

1. Data blocks overlap

processor or program

memory

2. Invalid block transfer

starting addresses

3. Replace 1771-M3

controller

References in reverse type are to the

notes in section titled "Monitoring the

Status Block".

Flashing

?

1. Switch settings.

2. Power down

reseat 1771ĆES

expander.

3. Replace 1771ĆES

expander.

1. 1771ĆES expander

switch settings.

2. Replace 1771ĆM3

controller

3. Replace 1771ĆES

expander(s).

1. Power down.

reseat 1771ĆES expander.

2. Cycle power at I/O chassis

3. Replace 1771ĆES

expander.

1. Cycle power at I/O chassis

2. Replace 1771ĆES

expander.

3. Replace 1771ĆM3 controller

1. Check I/O chassis

power supply.

2. Power down,

reseat 1771ĆM3

controller

3. Replace 1771ĆM3

controller.

Consult PC

installation

manual

OFF

ON

ON

OFF

OFF

YES

YES

NO

ON

OFF

ON

NO

NO

YES

YES

NO

A

11068 OS

1

2

3

2

2

2

1

1

1

4

2

2

2

2

2