Installing the Assembly

Chapter 6

6Ć12

Within a shielded cable, pairs of wires are twisted together. Using a
twisted pair for a signal and its return path provides further protection
against noise. We show a twisted pair like this:

We show a shielded twisted pair like this:

.

Connect each shield to ground at one end only. At the other end, cut the
shield foil and drain wire short and cover them with tape to protect against
their accidentally touching ground. Keep the length of leads extending
beyond the shield as short as possible.

Use cables with the proper number of individually shielded twisted pairs
as follows:

To connect to:

Number of

Individually

Shielded

Twisted Pairs: Use:

Encoder

4

Belden 8725 or equivalent

Analog power supply

2

Belden 8723 or equivalent

All other shielded cable

connections

1

Belden 8761 or equivalent

Connecting the Input Supply

To connect the input power supply, follow these steps:

1.

Connect the plus side of the input power supply to terminal 1 of the
left wiring arm.