Formatting and Interpreting Data Blocks

Chapter 7

7Ć7

Figure 7.4

First Status Word

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

First Status Word

11053

In-Position

Done

Ready

Jog + (Hardware start)

Slide Stop

Jog - (Feedrate

Override Enable)
Home

1 = Auto

0 = Manual

Excess Error

Loss of

Feedback

Insufficient

Data

+ Travel Limit

- Travel Limit

Feed Reduction

Hardware Stop

Immediate Stop

Word 3 (Axis 1)

Word 7 (Axis 2)

Word 11 (Axis 3)

Bit 0 InĆPosition

The 1771-M3 controller turns on this bit when following error is less than
twice the in-position band value programmed in the parameter block
(word 11). When the in-position bit is on, it indicates that the axis has
moved to within a specified distance of the programmed end point.

Bit 1 Done

The 1771-M3 controller turns on this bit when the 1771-ES expander has
finished feeding the axis for a programmed move or finished a dwell.

Bit 2 Ready

The 1771-M3 controller turns off the ready bit after power-up or after you
execute the reset command. The controller turns on this bit when it
receives valid parameter-block values. When the ready bit is on, the
1771-M3 controller is ready to respond to commands you issue through
the command block.