Installing the Assembly

Chapter 6

6Ć24

Connecting Drive Disable

Figure 6.13 shows details of how to connect drive disable for two basic
types of configurations. Some servo drives require a current source
connected to an input to enable the drive. Some require a current sink
connected to an input to enable the drive. We provide all three connection
points (base, emitter, and collector) of the drive disable circuit to provide
you with a flexibility of connecting it in a configuration that applies to
your servo drive.

Figure 6.13

Connection Details for Two Basic Drive Configurations

Q1

8.2k

+

-

Customer's Drive

Disable Power Supply

(5 to 30V dc)

Drive Disable

Input on Customer's

Servo Drive

8

9

10

a) Current Sourcing Configuration

Drive Enable Q1 on: Current is sourced

from terminal 10 into the servo drive.

Drive Disabled Q1 off: Current into the

servo drive is inhibited.

Q1

8.2k

+

-

8

9

10

Customer's Drive

Disable Power Supply

(5 to 30Vdc)

Drive Disable

Input on Customer's

Servo Drive

b) Current Sinking Configuration

Drive Enable Q1 on: Current is sunk thru

terminal 9 and Q1.

Drive Disabled Q1 off: Current thru Q1 is

inhibited. Terminal 9 is pulled up to the

potential of terminal 8.

12023

For the drive disable circuit, you must provide a 5-30V dc power supply
which can provide 100mA maximum. The power supply can be separate
or an integral part of the servo drive. Each of the configurations of figure
6.13 includes a separate power supply.