Publication 1794-UM064B-EN-P - May 2014

Configure the Adapter for Master/Slave Communication 89

The read configuration message response returns the current configuration data.
At power up, the configuration is the maximum read and write sizes supported by
each FLEX I/O module.

A valid check configuration message updates the internal configuration. The
updated internal configuration is then returned in the message response.

Refer to your configuration tool publications for information on how and where
to enter this data.

Chapter Summary

In this chapter you learned about input, output and configuration files. Read the
next chapter to learn how to troubleshoot your module.

Power Up Configuration Example

Read Configuration Message response at Power Up (Length 10 bytes)

Name

Identifier Byte

Description

Octet 1:

50h

Status Word (input – 1 word)

Octet 2:

60h

Output Status Word (output – 1 word)

Octet 3:

51h

Slot 1, input module 2 words

Octet 4:

60h

Slot 1, output module 1 word

Octet 5:

50h

Slot 2, input module empty

Octet 6:

61h

Slot 2, output module 1 word

Octet 7:

58h

Slot 3, input module 8 words

Octet 8:

65h

Slot 3, output module 1 word

Octet 9:

50h

Slot 4, input module empty

Octet 10:

65h

Slot 4, output module 6 words

I/O sizes configured: 22 input bytes, 12 output bytes