Connect the adapter to the network, Connect wiring to the adapter, Table cable types and descriptions on – Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 86

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

74 Connect Your Adapter to the PROFIBUS DP Network

Connect the Adapter to the
Network

For line A or B connections,

• use bus segments with t-junctions and termination blocks to form the

PROFIBUS media (trunk cable).

• Use termination blocks to terminate the line at each end of the trunk cable.
• Use drop cables to connect devices to the network.

The maximum number of stations on the same network is 32.

Connect Wiring to the Adapter

1. Connect the PROFIBUS drop cable to the 9-pin D-shell connector

according to the pin assignments in

Table D-Shell Pin Assignment on

page 75

.

Cable Types and Descriptions

Equipment

Type

Catalog Number

Part Number

Drop cable

Sprecher + Schuh

PTL-2, PTL-4, PDC-10

87.890.282-10

T-junction connector

Sprecher + Schuh

PTS-0

87.890.276-01

Bus segment cable

Sprecher + Schuh

none

299.257.001

Bus segment 1 m

Sprecher + Schuh

PCB-10

87.890.281-10

Connector

Sprecher + Schuh

none

87.890.283-01

Termination Block

Sprecher + Schuh

PCE-0

87.890.284-01

PROFIBUS DP
master/scanner
controller

PROFIBUS media
(trunk cable)

Other DP
adapter/slave

1794-APBDPV1 adapter/slave

FLEX I/O system

Other DP
adapter/slave

Personal computer
with configuration
software

1155

ATTENTION: If you connect or disconnect wiring while the field-side
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the
area is nonhazardous before proceeding.