Communicate With Your Module 33

1794-IT8 Word/Bit Descriptions

Word

Decimal Bit

Definition

Read Word 0

00…15 (00…17)

Reserved

Read Word 1

00…15 (00…17)

Channel 0 Input data

Read Word 2

00…15 (00…17)

Channel 1 Input data

Read Word 3

00…15 (00…17)

Channel 2 Input data

Read Word 4

00…15 (00…17)

Channel 3 Input data

Read Word 5

00…15 (00…17)

Channel 4 Input data

Read Word 6

00…15 (00…17)

Channel 5 Input data

Read Word 7

00…15 (00…17)

Channel 6 Input data

Read Word 8

00…15 (00…17)

Channel 7 Input data

Read Word 9

00…07 (00…07)

Underrange bits – These bits are set if the input signal is
below the input channel’s minimum range.

08…15 (10…17)

Overrrange bits – These bits are set if 1), the input signal
is above the input channel’s maximum range, or 2), an open
detector is detected.

Read Word 10

00

Not used – set to 0.

01

Cold Junction sensor underrange bit – This bit is set if
the cold junction temperature is below 0 °C.

02

Cold Junction sensor overrange bit – This bit is set if
the cold junction temperature is above 70 °C.

03

Power Up bit – This bit is set (1) until configuration data is
received by the module.

04…06

Critical Fault bits – If these bits are anything other than
zero, return the module to the factory for repair.

07

Unused – Set to 0.

08 (10)

Calibration Out of Range bit – Set to 1 if a reference
signal is out of range during calibration.

09 (11)

Calibration Done bit – Set to 1 after an initiated
calibration cycle is complete.

10 (12)

Calibration Bad bit – Set to 1 if the channel has not had a
valid calibration.

11…15 (13…17)

Unused – Set to 0.