Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 27

Publication 1794-UM064B-EN-P - May 2014
Communicate With Your Module 15
1794-IV16 – 16-point Source Input Module Image Table Mapping
1794-OB16 Memory Map
Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read/Write Words
Not used
Read Word 0
O15
O14
O13
O12
O11
O10
O9
O8
O7
O6
O5
O4
O3
O2
O1
O0
Write Word 0
Not used
Write Word 1
Where:
O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, and so on)
1794-IV16 Memory Map
Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read/Write Words
D15
D14
D13
D12
D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
Read Word 0
Counter
Read Word 1
Not used
DF
RC
NU
FT for all channels
Not used
Write Word 0
Where:
D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1, and so on)
DT = Input Filter Time (FT 00…11 corresponds to inputs 0…11; FT 12…15 corresponds to inputs 12…15)
DF = Disable Filter
RC = Reset Counter
NU = Not Used
FT for all
Channels
RC
DF
Counter
1132
1794-IV16 Input Filter Times
Description
Selected
Filter Time
10
09
08
Filter Time for Inputs 00-15 (00…17)
0
0
0
Filter Time 0 (default)
216 µs
0
0
1
Filter Time 1
512 µs
0
1
0
Filter Time 2
1 ms
0
1
1
Filter Time 3
2 ms
1
0
0
Filter Time 4
4 ms