Publication 1794-UM064B-EN-P - May 2014

Communicate With Your Module 15

1794-IV16 – 16-point Source Input Module Image Table Mapping

1794-OB16 Memory Map

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

Not used

Read Word 0

O15

O14

O13

O12

O11

O10

O9

O8

O7

O6

O5

O4

O3

O2

O1

O0

Write Word 0

Not used

Write Word 1

Where:

O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, and so on)

1794-IV16 Memory Map

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

D15

D14

D13

D12

D11

D10

D9

D8

D7

D6

D5

D4

D3

D2

D1

D0

Read Word 0

Counter

Read Word 1

Not used

DF

RC

NU

FT for all channels

Not used

Write Word 0

Where:

D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1, and so on)
DT = Input Filter Time (FT 00…11 corresponds to inputs 0…11; FT 12…15 corresponds to inputs 12…15)
DF = Disable Filter
RC = Reset Counter
NU = Not Used

FT for all

Channels

RC

DF

Counter

1132

1794-IV16 Input Filter Times

Description

Selected
Filter Time

10

09

08

Filter Time for Inputs 00-15 (00…17)

0

0

0

Filter Time 0 (default)

216 µs

0

0

1

Filter Time 1

512 µs

0

1

0

Filter Time 2

1 ms

0

1

1

Filter Time 3

2 ms

1

0

0

Filter Time 4

4 ms

Advertising