Publication 1794-UM064B-EN-P - May 2014

Configure the Adapter for Master/Slave Communication 83

When you use the condensed format, no safe state data can be defined, thus the
safe state data is left at the power up default of all zeroes. Setting the Fault Action
in the byte to Use Safe State with this format is the equivalent of setting Reset to
Zero.

The complete I/O module real time data table without the module ID, but with
the module configuration, is transferred via cyclic PROFIBUS data in one block.

Refer to your configuration tool publications for information on how and where
to enter this data.

1794-IP4/B

1A04h

1203-FM1

1600h

1794-IE8H/A

1E3F 2003h

1794-OE8H/A

153F 2002h

1797-IE8H/A

1E3F 2001h

1797-OE8H/A

153F 2002h

1794-VHSC/A

1A3F 2000h

1794-IF8IH/A

1E3F 2005h

1794-OF8I/A

153F 2006h

1794-IE8H/B

1E3F 2103h

1794-OE8H/B

153F 2104h

1797-IE8H/B

1E3F 2102h

1797-OE8H/B

153F 2102h

User Parameter Example

User Parameter Message, Condensed Format (Length 17 bytes)

Name

Value

Description

Octet 8:

02h

Condensed Format, Reset to Zero on Fault, Reset
Inputs to Zero

Octet 9-10:

0281h

1794-IB16 16-point discrete input module

Octet 11-12:

0191h

1794-OB16 16-point discrete output module

Octet 13-14:

1920h

1794-IE8 8-point analog input module

Octet 15-16:

1121h

1794-OE4 4-point analog output module

Octet 17-18:

0FFFFh

Empty

Octet 19-20:

0FFFFh

Empty

Octet 21-22:

0FFFFh

Empty

Octet 23-24:

0FFFFh

Empty

FLEX I/O Module Catalog Number

Module Identification Number
(module key)