Configure the Adapter for Master/Slave Communication 83
When you use the condensed format, no safe state data can be defined, thus the
safe state data is left at the power up default of all zeroes. Setting the Fault Action
in the byte to Use Safe State with this format is the equivalent of setting Reset to
Zero.
The complete I/O module real time data table without the module ID, but with
the module configuration, is transferred via cyclic PROFIBUS data in one block.
Refer to your configuration tool publications for information on how and where
to enter this data.
1794-IP4/B
1A04h
1203-FM1
1600h
1794-IE8H/A
1E3F 2003h
1794-OE8H/A
153F 2002h
1797-IE8H/A
1E3F 2001h
1797-OE8H/A
153F 2002h
1794-VHSC/A
1A3F 2000h
1794-IF8IH/A
1E3F 2005h
1794-OF8I/A
153F 2006h
1794-IE8H/B
1E3F 2103h
1794-OE8H/B
153F 2104h
1797-IE8H/B
1E3F 2102h
1797-OE8H/B
153F 2102h
User Parameter Example
User Parameter Message, Condensed Format (Length 17 bytes)
Name
Value
Description
Octet 8:
02h
Condensed Format, Reset to Zero on Fault, Reset
Inputs to Zero
Octet 9-10:
0281h
1794-IB16 16-point discrete input module
Octet 11-12:
0191h
1794-OB16 16-point discrete output module
Octet 13-14:
1920h
1794-IE8 8-point analog input module
Octet 15-16:
1121h
1794-OE4 4-point analog output module
Octet 17-18:
0FFFFh
Empty
Octet 19-20:
0FFFFh
Empty
Octet 21-22:
0FFFFh
Empty
Octet 23-24:
0FFFFh
Empty
FLEX I/O Module Catalog Number
Module Identification Number
(module key)