30 Communicate With Your Module

1794-IR8 Word/Bit Descriptions

Word

Dec. Bits
(Octal Bits)

Description

Write Word 0

00…01

Module Data Type

Bit

01

00

0

0

°C (default)

0

1

°F

1

0

Bipolar counts scaled between -32768... 32767

1

1

Unipolar counts scaled between 0...65535

02

Enhanced mode select – Measures voltage drop across a precision resistor in the module to compare
with the unknown input.

03…05

A/D Filter First Notch Frequency

Bit

05

04

03

Definition

0

0

0

10 Hz (default)

0

0

1

25 Hz

0

1

0

50 Hz

0

1

1

60 Hz

1

0

0

100 Hz

1

0

1

250 Hz

1

1

0

500 Hz

1

1

1

1000 Hz

06

Gain Offset Calibration – This bit is set during gain calibration/ reset during offset calibration.

07

Calibration Clock – This bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.

08…15

Calibration Mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0
corresponds to channel 0, bit 1 to channel 1, and so on.

Advertising