Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 42

Publication 1794-UM064B-EN-P - May 2014
30 Communicate With Your Module
1794-IR8 Word/Bit Descriptions
Word
Dec. Bits
(Octal Bits)
Description
Write Word 0
00…01
Module Data Type
Bit
01
00
0
0
°C (default)
0
1
°F
1
0
Bipolar counts scaled between -32768... 32767
1
1
Unipolar counts scaled between 0...65535
02
Enhanced mode select – Measures voltage drop across a precision resistor in the module to compare
with the unknown input.
03…05
A/D Filter First Notch Frequency
Bit
05
04
03
Definition
0
0
0
10 Hz (default)
0
0
1
25 Hz
0
1
0
50 Hz
0
1
1
60 Hz
1
0
0
100 Hz
1
0
1
250 Hz
1
1
0
500 Hz
1
1
1
1000 Hz
06
Gain Offset Calibration – This bit is set during gain calibration/ reset during offset calibration.
07
Calibration Clock – This bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.
08…15
Calibration Mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0
corresponds to channel 0, bit 1 to channel 1, and so on.