Communicate With Your Module 63

1794-IP4 – Pulse Counter Module Image Table Mapping

1794-IP4 Pulse Counter Module Block Transfer Word Assignments

(Octal Bit

⇒ )

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Dec. Bit

15

14

13

12

11

10

03

08

07

06

05

04

03

02

01

00

Word

Read

1

Ch 0 Data 0 – 16-bit period measurement or low word of 32-bit period measurement for channel 0.

2

Ch 0 Data 1 – pulse counter or high word of 32-bit period measurement for channel 0.

3

Ch 1 Data 0 – 16-bit period measurement or low word of 32-bit period measurement for channel 1.

4

Ch 1 Data 1 – pulse counter or high word of 32-bit period measurement for channel 1.

5

Ch 2 Data 0 – 16-bit period measurement or low word of 32-bit period measurement for channel 2.

6

Ch 2 Data 1 – pulse counter or high word of 32-bit period measurement for channel 2.

7

Ch 3 Data 0 – 16-bit period measurement or low word of 32-bit period measurement for channel 3.

8

Ch 3 Data 1 – pulse counter or high word of 32-bit period measurement for channel 3.

9

Status.

Reserved.

RD3

RD2

RD1

RD0

Ch 3
Ready

Ch 2
Ready

Ch 1
Ready

Ch 0
Ready

10

Revision read – software version code.