Publication 1794-UM064B-EN-P - May 2014

40 Communicate With Your Module

Write Word 1

04…05

Sensor Mode Select bits

Bit

05

04

Sensor mode select for channels 0...3

Thermocouple

0

0

External compensation – uses cold junction sensors

0

1

Internal compensation – uses the value selected for "reference junction selection"

1

0

No compensation (Data is referenced to 0 °C)

1

1

Differential measurement between 2 channels (0…1, 2…3, 4…5, 6…7)

RTD

0

0

1-wire RTD no compensation

0

1

2-wire RTD with user selected compensation

1

0

3-wire RTD

1

1

4-wire RTD

06…07

Sensor

Bit

07

06

Input type selection for channels 0…3

0

0

Thermocouple

0

1

RTD

1

0

Not used

1

1

08…11
(10…13)

Sensor Mode Select bits

RTD Type

Bit

11

10

09

08

Sensor type for channels 4...7

0

0

0

0

Resistance (default)

0

0

0

1

100

Ω Pt α = 0.00385 Euro (-200...870 °C)

0

0

1

0

200

Ω Pt α = 0.00385 Euro (-200...400 °C)

0

0

1

1

100

Ω Pt α = 0.003916 U.S. (-200...630 °C)

0

1

0

0

200

Ω Pt α = 0.003916 U.S. (-200...400 °C)

0

1

0

1

100

Ω Nickle (-60...250 °C)

0

1

1

0

200

Ω Nickle (-60...200 °C)

0

1

1

1

120

Ω Nickle (-80...320 °C)

1

0

0

0

10

Ω Copper (-200...260 °C)

1001...1111 not used

Word

Dec. Bits
(Octal Bits)

Description