Publication 1794-UM064B-EN-P - May 2014

Communicate With Your Module 11

• node address changed — 1 bit

The adapter input status word bit descriptions are shown in

Table Input Status

Word Bits

.

Possible causes for an I/O module fault are:

• transmission errors on the FLEX I/O backplane
• a failed module
• a module removed from its terminal base
• an incorrect module inserted in a slot position
• an empty slot

The node address changed bit is set when the node address switch setting has
been changed since power up. The new node address does not take effect until
the adapter has been powered down and then powered back up. Until this power
cycling occurs, the node address switches will not match the actual node address.

Input Status Word Bits

Bit Description

Bit

Explanation

I/O Module Fault

8

This bit is set (1) when an error is detected in slot position 1.

9

This bit is set (1) when an error is detected in slot position 2.

10

This bit is set (1) when an error is detected in slot position 3.

11

This bit is set (1) when an error is detected in slot position 4.

12

This bit is set (1) when an error is detected in slot position 5.

13

This bit is set (1) when an error is detected in slot position 6.

14

This bit is set (1) when an error is detected in slot position 7.

15

This bit is set (1) when an error is detected in slot position 8.

Reserved

1…7

Reserved

Node Address
changed

0

This bit is set (1) when the node address switch setting has been
changed since power up.

I/O Module Fault Bits

Reserved

Node Address Changed Bit

Bit:

15

0

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

Slot 8