Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 53

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

Communicate With Your Module 41

Write Word 1

08…11
(10…13)

Thermocouple Type

Bit

11

10

09

08

Sensor type for channels 4...7

0

0

0

0

mV (default)

0

0

0

1

B 300...1800 °C (572...3272 °F)

0

0

1

0

E -270...1000 °C (-454...1835 °F)

0

0

1

1

J -210...1200 °C (-346...2192 °F)

0

1

0

0

K -270...1372 °C (-454...2502 °F)

0

1

0

1

TXK/XK(L) -200...800 °C (-328...1472 °F)

0

1

1

0

N -270...1300 °C (-450...2372 °F)

0

1

1

1

R -50...1768 °C (-58...3214 °F)

1

0

0

0

S -50...1768 °C (-58...3214 °F)

1

0

0

1

T -270...400 °C (-454...752 °F)

1010...1111 not used

12…13
(14…15)

Sensor Mode Select bits

Bit

13

12

Sensor mode select for channels 4…7

Thermocouple Type

0

0

External compensation – uses cold junction sensor.

0

1

Internal compensation – uses the value selected for reference junction.

1

0

No compensation (Data is referenced to 0 °C).

1

1

Differential measurement between 2 channels.

RTD

0

0

2-wire RTD no compensation.

0

1

2-wire RTD with loop resistance compensation.

1

0

3-wire RTD.

1

1

4-wire RTD.

14…15
(16…17)

Sensor

Bit

15

14

Input type selection for channels 4…7

0

0

Thermocouple.

0

1

RTD.

1

0

Not used.

1

1

Word

Dec. Bits
(Octal Bits)

Description

Advertising