72 Connect Your Adapter to the PROFIBUS DP Network

Cabling and Equipment
Required for Line A Type

Line A cabling can support baudrates as high as 1.5 Mbits/s.

Cables

You need a shielded twisted pair cable for your cabling (bus segments or drop
cables). Any line A cable available on the market can be used to connect your
adapter to a PROFIBUS network.

T-junction Connectors

You need t-junction connectors to connect your droplines to bus segments. You
can use any t-junctions available on the market.

Termination Blocks

Termination blocks are only needed if the devices on the end of the network do
not have built-in terminating resistors. If you need termination blocks, you can
use any termination blocks available on the market.

Maximum
Length
with Baud
Rate
(bits/s) of:

≤ 19.2

k

1200 m

1200 m

≤ 15 nF

93.75 k

1200 m

1200 m

≤ 3 nF

187.5 k

1000 m

600 m

≤ 1 nF

500 k

400 m

200 m

≤ 0.6 nF

1.5 M

200 m

NA

≤ 0.2 nF

12 M

100 m

Where:

NA = Not Applicable

(1)

Measurements are the sum of all bus segments and drop cable lengths combined.

(2)

If using a combination of both line types, divide the lengths shown by two.

Line Type Characteristics

Characteristic

Bus Segments and Drop Cables

(1)

Line A Requirements

(2)

Line B Requirements

Total Capacity of
all Drop Cables

Impedance

135…165

Ω (3-29 MHz) 100…130 Ω (f> 100 kHz)