Enter user parameter data, User parameter data – Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 92

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

80 Configure the Adapter for Master/Slave Communication

Enter User Parameter Data

Send parameter data is comprised of a string of octets (1…244) that contain 244
bytes of data:

• octets 1…7 contain data specific to the:

– PROFIBUS Standard
– defaults contained in the database (GSD) file

• octets 8…244 are user configurable and contain user parameter data. User

parameter data consists of these formats:
– auto configure
– condensed
– full

Figure Send Parameter Data Table Structure shows the structure of the send
parameter data table.

Send Parameter Data Table Structure

User Parameter Data

The first byte of the user parameter data is the flags byte. This byte selects the
appropriate format and also specifies adapter behavior. The flags byte is defined
in the following table:

If the send parameter data is received with no user parameter data, the flags byte
is set to zero which selects:

Group

Ident.

Number

Minimum

Station

Delay

Watchdog
Control

Station

Status

User Parameter Data

Watchdog
Control

You configure these values using your

software configuration tool.

These values are defined by the PROFIBUS

standard. the defaults are provided by

the GSD file.

Ident.

1161

Send Parameter Data Flags Byte

Bit Position

Name

Description

0…1

Format Selection

00 = Auto Configure
01 = Reserved
10 = Condensed
11 = Full

2…3

Fault Action

00 = Reset to zero
01 = Hold Last State
10 = Use Safe State
11 = Reserved

4

Input Fault Action

0 = Reset inputs to zero
1 = Hold Last Value

5

Byte Order of Float values

6…7

Reserved

Reserved bits must be zero