Communicate With Your Module 21

1794-IE8/B Range Selection Bits

Channel No.

Channel 0

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

F0

C0

F1

C1

F2

C2

F3

C3

F4

C4

F5

C5

F6

C6

F7

C7

Decimal Bits
(Octal Bits)

00

08
(10)

01

09
(11)

02

10
(12)

03

11
(13)

04

12
(14)

04

13
(15)

06

14
(16)

07

15
(17)

0…10V DC/0…20 mA

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

4…20 mA

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

-10…10V DC

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Off

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Where:

C = Configure select bit
F = Full range bit
Off = When configured to off, individual channels will return 0000H on Series B modules, and 4…20 mA on Series A modules.

1794-IE8 Word/Bit Descriptions

Word

Decimal Bit

Definition

Read Word 0

Bits 00…14

Channel 0 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 0 analog data sign bit.

Read Word 1

Bits 00…14

Channel 1 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 1 analog data sign bit.

Read Word 2

Bits 00…14

Channel 2 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 2 analog data sign bit.

Read Word 3

Bits 00…14

Channel 3 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 3 analog data sign bit.

Read Word 4

Bits 00…14

Channel 4 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 4 analog data sign bit.

Read Word 5

Bits 00…14

Channel 5 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 5 analog data sign bit.

Read Word 6

Bits 00…14

Channel 6 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 6 analog data sign bit.

Read Word 7

Bits 00…14

Channel 7 analog data – 12-bit left justified two’s complement number;
unused lower bits are zero; 4…20 mA uses all 16 bits.

Bit 15

Channel 7 analog data sign bit.