Publication 1794-UM064B-EN-P - May 2014

118 Device Data Base (GSD) File

5. Once the modules are added and configured, download the configuration

and go online. After the Adapter Status LED and Profibus Status LED
light up solid green, then disconnect the connection.

6. Delete the slave (adapter) from the configuration tool right window pane.

7. Now load the Standard GSD (*_standard.gsd) file you have created in the

previous section.

8. Drag the standard GSD file from the left window pane to the right

window pane as shown in the following picture.

9. Add the adapter status. Then, add standard module 1794-OV16P in Full

format as shown in the following picture.