Publication 1794-UM064B-EN-P - May 2014

10 Communicate With Your Module

For example, a 16 point discrete input module will have up to 2 read words and 1
write word.

Refer to each module user manual I/O map for the exact mapping.

Polled I/O Structure

The first word of output data received by the adapter is the Adapter Status Word.
Output data is received by the adapter in the order of the installed I/O modules.
The Output data for Slot 1 is received first, followed by the Output data for
Slot 2, and so on up to slot 8. All bits in the output status word are reserved.

The first word of input data sent by the adapter is the Adapter Status Word. This
is followed by the input data from each slot, in the order of the installed I/O
modules. The Input data from Slot 1 is first after the status word, followed by
Input data from Slot 2, and so on up to slot 8.

Adapter Input Status Word

The input status word consists of:

• I/O module fault bits — 1 status bit for each slot

Delay

Time

Delay

Time

1123

16-point Discrete Input Module

Adapter Status

Read

Write

Slot 1 Input Data

Slot 2 Input Data

Slot 8 Input Data

Adapter Status

Slot 1 Output Data

Slot 2 Output Data

Slot 8 Output Data

1124