Publication 1794-UM064B-EN-P - May 2014

Connect Your Adapter to the PROFIBUS DP Network 75

2. Connect the cable shield to pin 1.

The shield is connected to earth ground.

3. Connect the data signal pins on both ends (signal + pin 3 and

signal - pin 8).

4. Insert the wired connector into the mating connector on the PROFIBUS

adapter as shown.

D-Shell Pin Assignment

PIN

RS-485 Reference

Signal

Description

1

Shield

Shield, RC to earth ground

2

RP

Not used

3

B/B’

RXD/TXD-P

Receive/transmit data - P

4

CTNR-P

Not used

5

C/C’

DGND

Data ground

6

VP

Voltage plus (+5V)

7

PR

Not used

8

A/A’

RXD/TXD-N

Receive/transmit data - N

9

CTNR-N

Not used

Metal shell

Earth ground

1

.

.

Data ground

Shield

Pin #1

5

RCV/ Xmit data +

9

6

.

.

DROP CABLE

PROFIBUS

ADAPTER

Signal + Pin #3

Pin #5

+5V Pin #6

Signal - Pin #8

Earth ground

RCV/ Xmit data -

.

*

Pins #5 and #6 can be used to supply an external PROFIBUS terminator.

*