Publication 1794-UM064B-EN-P - May 2014

114 Device Data Base (GSD) File

Byte 8

The length of digital inputs in bits.

For digital input modules, the length of digital inputs, based on

Example RTD I/O Profile for Sample EDT Module on page 112

, is

0x80(I:0 toI:7).

For analog input modules and non-input modules, this byte is 0x00.

Byte 9

The start address of analog input in bits.

For analog input modules, the start address (in bits) of input (RTD2),
based on

Example RTD I/O Profile for Sample EDT Module on page

112

, is 16(RTD0) + 16 (RTD1) = 32 bits, that is, 0x20.

For digital input modules and non-input modules, this byte is 0x00.

Byte 10

The length of analog inputs in bits.

For analog input modules, the length of analog inputs,

Example

RTD I/O Profile for Sample EDT Module on page 112

, is 0x80(I:0 to

I:7).

For digital input modules and non-input modules, this byte is 0x00.

Byte 11

The start address of Status information in bits.

Based on

Example RTD I/O Profile for Sample EDT Module on page

112

, the start address (in bits) of Status Information (RTD10) is

16(RTD0) + 16(RTD1) + 128(RTD2…RTD9) = 160 bits, that is, 0xA0.

If there is no Status Information byte in above I/O profile table then
this byte is 0x00.

Byte 12

The length of Status Information in bits.

Based on

Example RTD I/O Profile for Sample EDT Module on page

112

, the length (in bits) is 32(2 words, S0 .. S1), that is, 0x20.

If there is no Status Information byte in the I/O profile table then
this byte is 0x00.

Byte 13

The start address of digital output in bits.

For digital output modules, the start address (in bits) of output
(RTD13) based on

Example RTD I/O Profile for Sample EDT Module

on page 112

, is 16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32

(RTD10…RTD11) + 16(RTD12) = 208 bits, that is, 0xD0.

For analog output modules and non-output modules, this byte is
0x00.

Byte 14

The length of digital output in bits.

For digital input modules, the length of digital output, based on

Example RTD I/O Profile for Sample EDT Module on page 112

, is

0x10(O:0).

For analog output modules and non-output modules, this byte is
0x00.

Byte 15

The start address of analog output in bits.

For analog output module, the start address (in bits) of output
(RTD13) based on

Example RTD I/O Profile for Sample EDT Module

on page 112

, is 16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32

(RTD10…RTD11) + 16(RTD12) = 208 bits, that is, 0xD0.

For digital output modules and non-output modules, this byte is
0x00.

Byte 16

The length of analog output in bits.

For analog output modules, the length of analog output, based on

Example RTD I/O Profile for Sample EDT Module on page 112

, is

0x10(O:0).

For digital output modules and non-output modules, this byte is
0x00.

Byte 17

The start address of Configuration in bits.

Based on

Example RTD I/O Profile for Sample EDT Module on page

112

, the start address (in bits) of configuration (RTD14) will be

16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32 (RTD10…RTD11) +
16(RTD12) + 16 (RTD13) = 224 bits, that is, 0xE0.

If there is no Configuration Information byte in the RTD I/O profile
table, then this byte is 0x00.

Ext_User_Prm_Data_Const(0) Byte Description and Examples for EDT Modules