Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 126

Publication 1794-UM064B-EN-P - May 2014
114 Device Data Base (GSD) File
Byte 8
The length of digital inputs in bits.
For digital input modules, the length of digital inputs, based on
Example RTD I/O Profile for Sample EDT Module on page 112
, is
0x80(I:0 toI:7).
For analog input modules and non-input modules, this byte is 0x00.
Byte 9
The start address of analog input in bits.
For analog input modules, the start address (in bits) of input (RTD2),
based on
Example RTD I/O Profile for Sample EDT Module on page
112
, is 16(RTD0) + 16 (RTD1) = 32 bits, that is, 0x20.
For digital input modules and non-input modules, this byte is 0x00.
Byte 10
The length of analog inputs in bits.
For analog input modules, the length of analog inputs,
Example
RTD I/O Profile for Sample EDT Module on page 112
, is 0x80(I:0 to
I:7).
For digital input modules and non-input modules, this byte is 0x00.
Byte 11
The start address of Status information in bits.
Based on
Example RTD I/O Profile for Sample EDT Module on page
112
, the start address (in bits) of Status Information (RTD10) is
16(RTD0) + 16(RTD1) + 128(RTD2…RTD9) = 160 bits, that is, 0xA0.
If there is no Status Information byte in above I/O profile table then
this byte is 0x00.
Byte 12
The length of Status Information in bits.
Based on
Example RTD I/O Profile for Sample EDT Module on page
112
, the length (in bits) is 32(2 words, S0 .. S1), that is, 0x20.
If there is no Status Information byte in the I/O profile table then
this byte is 0x00.
Byte 13
The start address of digital output in bits.
For digital output modules, the start address (in bits) of output
(RTD13) based on
Example RTD I/O Profile for Sample EDT Module
on page 112
, is 16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32
(RTD10…RTD11) + 16(RTD12) = 208 bits, that is, 0xD0.
For analog output modules and non-output modules, this byte is
0x00.
Byte 14
The length of digital output in bits.
For digital input modules, the length of digital output, based on
Example RTD I/O Profile for Sample EDT Module on page 112
, is
0x10(O:0).
For analog output modules and non-output modules, this byte is
0x00.
Byte 15
The start address of analog output in bits.
For analog output module, the start address (in bits) of output
(RTD13) based on
Example RTD I/O Profile for Sample EDT Module
on page 112
, is 16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32
(RTD10…RTD11) + 16(RTD12) = 208 bits, that is, 0xD0.
For digital output modules and non-output modules, this byte is
0x00.
Byte 16
The length of analog output in bits.
For analog output modules, the length of analog output, based on
Example RTD I/O Profile for Sample EDT Module on page 112
, is
0x10(O:0).
For digital output modules and non-output modules, this byte is
0x00.
Byte 17
The start address of Configuration in bits.
Based on
Example RTD I/O Profile for Sample EDT Module on page
112
, the start address (in bits) of configuration (RTD14) will be
16(RTD0) + 16 (RTD1) + 128 (RTD2…RTD9) + 32 (RTD10…RTD11) +
16(RTD12) + 16 (RTD13) = 224 bits, that is, 0xE0.
If there is no Configuration Information byte in the RTD I/O profile
table, then this byte is 0x00.
Ext_User_Prm_Data_Const(0) Byte Description and Examples for EDT Modules