Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 60
Advertising
![background image](/manuals/580412/60/background.png)
Publication 1794-UM064B-EN-P - May 2014
48 Communicate With Your Module
1794-OF4I – 4-Output Isolated Analog Module Image Table Mapping
1148
1794-OF4I Isolated Analog Output Module Read Words
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Word 0
Read Back Channel 0
Read Word 1
Read Back Channel 1
Read Word 2
Read Back Channel 2
Read Word 3
Read Back Channel 3
Read Word 4
PU
FP
CF
0
Reserved
0
0
0
0
0
BD
DN
0
Read Word 5
0
0
0
0
P3
P2
P1
P0
0
0
0
0
W3
W2
W1
W0
Write Word 0
EN
S1
S0
0
0
0
0
0
0
0
0
0
0
0
0
0
Write Word 1
Output Data – Channel 0
Write Word 2
Output Data – Channel 1
Write Word 3
Output Data – Channel 2
Write Word 4
Output Data – Channel 3
Write Word 5
Output Ch 3
Configuration
Output Ch 2
Configuration
Output Ch 1
Configuration
Output Ch 0
Configuration