128 Additional HART Protocol Information

Common Practice Commands

Command

Data in Command

Data in Reply

#

Function

Byte

Data

Type

(5)

Byte

Data

Type

(5)

33

Read transmitter
variables

None

(2)

0

Transmitter variable code
for slot 0

1

Units code for slot 0

2…5

Variable for slot 0

(F)

6

Transmitter variable code
for slot 1

7

Units code for slot 1

8…11

Variable for slot 1

(F)

12

Transmitter variable code
for slot 2

(6)

13

Units code for slot 2

14…17

Variable for slot 2

(F)

18

Transmitter variable code
for slot 3

19

Units code for slot 3

20…23

Variable for slot 3

(F)

34

Write damping value

0…3

Damping value (seconds)

(F)

As in command

(F)

35

Write range values

0

Range units code

As in command

(F)

1…4

Upper range value

(F)

5…8

Lower range value

(F)

36

Set upper range value
(push SPAN button)

None

None

37

Set lower range value
(push ZERO button)

None

None

38

Reset configuration
changed flag

None

None

39

EEPROM control

0

(1)

EEPROM control code

As in command

40

Enter/edit fixed current
mode

0…3

Current (mA)

(3)

(F)

As in command

41

Perform device
self-test

None

None

42

Perform master reset

None

None

43

Set (trim) PV zero

None

None

44

Write PV units

0

PV units code

As in command

45

Trim DAC zero

0…3

Measured current (mA)

As in command

46

Trim DAC gain

0…3

Measured current (mA)

(F)

As in command

47

Write transfer function

0

Transfer function code

As in command