86 Configure the Adapter for Master/Slave Communication

Refer to your configuration tool publications for information on how and where
to enter this data.

Enter Check Configuration
Data

On a PROFIBUS DP network, the I/O data exchanged between the
PROFIBUS DP master and a DP slave is encapsulated into logical modules. The
total I/O data exchanged between a PROFIBUS DP master and a DP slave
device comprises a set of logical modules which is defined in the check
configuration data.

Each physical slot of the FLEX I/O system is represented by two logical modules
(one input and one output). When the FLEX I/O adapter is powered-up, the
check configuration message configures the module format (input and output
words) and defines the size of the modules within the device. When the sizes are
configured, the I/O data can be optimized to remove unused data from the data
stream.

Both input and output sizes can be configured. If a slot is empty, or if either the
input or output module is zero length, the specific identifier for an empty module
(free place) must be used.

If the end of the identifiers is reached before all slots have been configured, the
remaining slots are configured as empty.

The first two modules allocated are for the adapter itself, and must always be a 1
word input module and a 1 word output module, regardless of what parameter
format you choose. The adapter uses these words for adapter status information.
Modules for each of the individual slots (FLEX I/O modules) must also follow
these word assignments.

Octet 33…34:

0000h

output point 2

Octet 35…36:

0000h

output point 3

Octet 37…38:

0000h

output point 4

Octet 39…40:

0FFFFh

Slot 5 empty

Octet 41:

00h

Slot 5 all sizes zero

Octet 42…43

0FFFFh

Slot 6 empty

Octet 44:

00h

Slot 6 all sizes zero

Octet 45…46:

0FFFFh

Slot 7 empty

Octet 47:

00h

Slot 7 all sizes zero

Octet 48…49:

0FFFFh

Slot 8 empty

Octet 50:

00h

Slot 8 all sizes zero

User Parameter Example

User Parameter Message, Full Format (Length 43 bytes)

Name

Value

Description