Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 41

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

Communicate With Your Module 29

1794-IR8 Word/Bit Descriptions

Word

Decimal Bit

Definition

Read Word 0

00…15 (00…17)

Reserved

Read Word 1

00…15 (00…17)

Channel 0 Input data

Read Word 2

00…15 (00…17)

Channel 1 Input data

Read Word 3

00…15 (00…17)

Channel 2 Input data

Read Word 4

00…15 (00…17)

Channel 3 Input data

Read Word 5

00…15 (00…17)

Channel 4 Input data

Read Word 6

00…15 (00…17)

Channel 5 Input data

Read Word 7

00…15 (00…17)

Channel 6 Input data

Read Word 8

00…15 (00…17)

Channel 7 Input data

Read Word 9

00…07

Underrange bits – these bits are set if the input signal is below the input
channel’s minimum range.

08 …15 (10…17)

Overrrange bits – these bits are set if 1), the input signal is above the
input channel’s maximum range, or 2), an open detector is detected.

Read Word 10

00…01

Not used – set to 0

02

Reserved

03

Power Up bit – this bit is set (1) until configuration data is received by the
module.

04…06

Critical Error bits – If these bits are anything other than all zeroes, return
the module to the factory for repair.

07

Unused – set to 0

08 (10)

Calibration Out of Range bit – set to 1 if a reference signal is out of
range during calibration.

09 (11)

Calibration Done bit – set to 1 after an initiated calibration cycle is
complete.

10 (12)

Calibration Bad bit – set to 1 if the channel has not had a valid
calibration.

11…15 (13…17)

Unused – set to 0.