Communicate With Your Module 61

Write Word 1 Bit 04

Ch 0 Z Preset Enable bit – When this bit is set (1), a positive edge on Z preloads Counter X = Preset X, independent of
Cal Enable.
NOTE: If Z is configured to do Store and Preset (Reset), the Store will occur first.

Bit 05

Ch 0 Count Enable bit – When this is set (1), the incremental encoder is enabled.

Bits 06…08
(06…10)

Ch 0 Calibration Control bits – bits 06, 07 and 08.

06

Cal Enable bit – When set (1), the counter can be calibrated.

07

Cal Direction bit – When set (1), calibration is performed in a negative direction; when reset (0), calibration is
performed in a positive direction.

08

Ch 0 Cal Reset bit – Calibration is acknowledged and a new calibration is enabled on a positive edge on this bit.

Bits 09…10
(11…12)

10

09

Gate Control bits

0

0

No gate function on input G.

0

1

Counting only if G is high (active).

1

0

Counting only if G is low (inactive).

1

1

The counter can be calibrated when G is high (active).

Bits 11…12
(13…14)

12

11

Store Control bits

Save the counter value on positive edge of Z (if Stored X = 0).

Save the counter value on positive edge of G (if Stored X = 0).

Save the counter value on negative edge of G (if Stored X = 0).

Save the counter value on positive and negative edges of G (if Stored X = 0).

Bit 13 (15)

Ch 0 Rollover bit – When set (1), the counter counts up to the prset and then restarts at 0. If this bit is reset (0) (not
rollover), the rollover preset value = FFFF (hex = 65536 (decimal).

Bit 14 (16)

Ch 0 Store Reset bit – A positive edge on this bit resets Stored X in Signals.

Bit 15 (17)

Ch 0 Preset Reset bit – A positive edge on this bit resets Preset Detected in Signals.

Write Word 2

Ch 1 Control – Control word for setting the fuction of Ch 1 Counter.

Bits 00…02

Bit

02

01

00

Ch 1 Mode Selection bits

0

0

0

Counting on positive (rising) edge of input signal A (up/dwn counting determined by B).

0

0

1

Quadrature encoder X1.

0

1

0

Quadrature encoder X2.

0

1

1

Quadrature encoder X4.

1

0

0

Counting up on the positive edge of input signal A, and down on positive edge of input signal B.

1

0

1

No count function.

1

1

0

No count function.

1

1

1

No count function.

1794-ID2 Pulse Counter Module Word/Bit Definitions for Block Transfer Read Words