Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 67

Publication 1794-UM064B-EN-P - May 2014
Communicate With Your Module 55
Setting the Input Filters
Bits
Channel
03
02
01
00
Input Channel 0
07
06
05
04
Input Channel 1
A/D Conversion Rate
Low Pass Filter
0
0
0
0
1200 Hz
No low pass
0
0
0
1
1200 Hz
100 ms low pass
0
0
1
0
1200 Hz
500 ms low pass
0
0
1
1
1200 Hz
1000 ms low pass
0
1
0
0
600 Hz
No low pass
0
1
0
1
600 Hz
100 ms low pass
0
1
1
0
600 Hz
500 ms low pass
0
1
1
1
600 Hz
1000 ms low pass
1
0
0
0
300 Hz
No low pass
1
0
1
0
300 Hz
100 ms low pass
1
0
1
1
300 Hz
500 ms low pass
1
1
0
0
300 Hz
1000 ms low pass
1
1
0
1
150 Hz
No low pass
1
1
1
0
150 Hz
100 ms low pass
1
1
1
1
150 Hz
500 ms low pass
150 Hz
1000 ms low pass
(2)
<and> indicates the overrun beyond actual range (about 5%).
Configure Your Output Channels
Configuration Bits
MSD LSD
Nominal
Range
Data Type
Output Values
Hexadecimal Decimal
Update
Rate
0
0
0
1
4...20 mA
2’s complement
<0000...7878>
<0000...30840>
5.0 ms
0
0
1
0
± 10V
2’s complement
<8618...79E8>
<-31208...31208>
2.5 ms
0
0
1
1
± 5V
2’s complement
<8618...79E8>
<-31208...31208>
2.5 ms
0
1
0
0
0...20 mA
2’s complement %
<0...10000>
<0...10000>
5.0 ms
0
1
0
1
4...20 mA
2’s complement %
<0...10000>
<0...10000>
5.0 ms
0
1
1
0
0...10V
2’s complement %
<0...10000>
<0...10000>
5.0 ms
0
1
1
1
± 10V
2’s complement
<-10000...10000>
<-10000...10000>
5.0 ms
1
0
0
0
0...20 mA
binary
<0000...F3CF>
<0000...62415>
2.5 ms
1
0
0
1
4...20 mA
binary
<0000...F0F1>
<0000...61681>
5.0 ms
1
0
1
0
0...10V
binary
<0000...F3CF>
<0000...62415>
2.5 ms
1
0
1
1
0...5V
binary
<0000...F3CF>
<0000...62415>
2.5 ms
1
1
0
0
4...20 mA
offset binary
<8000...F9E8>
<32768...63976>
2.5 ms