Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 49

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

Communicate With Your Module 37

Sensor
Ch 4…7

Sensor
Mode
Ch 4…7

Sensor Type Ch 4…7

Sensor Ch 0…3

Sensor Mode
Ch 0…3

Sensor Type Ch 0…3

Write 1

RTD Offset
Ch 7

RTD Offset
Ch 6

RTD Offset
Ch 5

RTD Offset
Ch 4

RTD Offset
Ch 3

RTD Offset
Ch 2

RTD Offset
Ch 1

RTD Offset
Ch 0

Write 2

EDT command

EDT command data

Write 3

1794-IRT8 Word/Bit Descriptions for Block Transfer Words

Word

Decimal Bit

Definition

Read Word 0

00…15 (00…17)

Channel 0 Input data

Read Word 1

00…15 (00…17)

Channel 1 Input data

Read Word 2

00…15 (00…17)

Channel 2 Input data

Read Word 3

00…15 (00…17)

Channel 3 Input data

Read Word 4

00…15 (00…17)

Channel 4 Input data

Read Word 5

00…15 (00…17)

Channel 5 Input data

Read Word 6

00…15 (00…17)

Channel 6 Input data

Read Word 7

00…15 (00…17)

Channel 7 Input data

Read Word 8

00…07

Underrange bits – These bits are set if the input signal is below the input
channel’s minimum range. Bit 00 corresponds to channel 0, bit 01
corresponds to channel 1, and so on.

08…15 (10…17)

Overrange bits – These bits are set if 1), the input signal is above the
input channel’s maximum range, or 2), an open detector is detected. Bit 08
(10) corresponds to channel 0, bit 09 (11) corresponds to channel 1,
and so on.

1794-IRT8 Thermocouple/RTD/mV Input Module Read Words

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write
Words

Advertising