Publication 1794-UM064B-EN-P - May 2014

38 Communicate With Your Module

1794-IRT8 Word/Bit Descriptions for Block Transfer Words

Word

Dec. Bits
(Octal Bits)

Description

Write Word 0

00…02

Inpt Filter Cutoff Bits

Bit

02

01

00

Filter Time Constants – Actual filtering depends on the module’s mode
of operation.

0

0

0

Hardware filtering only (default filtering).

0

0

1

25 ms

0

1

0

100 ms

0

1

1

250 ms

1

0

0

500 ms

1

0

1

1 s

1

1

0

2 s

1

1

1

5 s

03…05

Reference Junction Used when input type is set to thermocouple and sensor mode is set to internal
compensation. Sets a fixed reference junction to compensate all thermocouple channels.

Bit

05

04

03

Reference Junction

0

0

0

0 °C

0

0

1

20 °C

0

1

0

25 °C

0

1

1

30 °C

1

0

0

40 °C

1

0

1

50 °C

1

1

0

60 °C

1

1

1

70 °C

06…07

Fault Mode Bits When a bit is set (1), fault mode is enabled for that channel. Bit 06 corresponds to
channels 0…3; bit 07 corresponds to channels 4…7.
0 = disabled
1 = enable wire-off detection

08…11
(10…13)

Data Format – Module defaults to -4000...10000 in millivolt mode, and 0...5000 in ohms mode with implied
decimal points (for example -40.00, 0.0

Ω ).

Bit

11

10

09

08

Data type for channels 0-7

0

0

0

0

°C (implies decimal point XXXX.X)

0

0

0

1

°F (implies decimal point XXXX.X)

0

0

1

0

°K (implies decimal point XXXX.X)

0

0

1

1

-32767...3267

0

1

0

0

0...65535

0101...1111 not used

12…15
(14…17)

Not used