92 Interpret Status Indicators for the FLEX I/O PROFIBUS Module

View status from the
Master’s Configuration
Software

You can use read diagnostics to view status using the master’s configuration
software. The adapter returns identification in response to the Read DP–Slave
Diagnostic Information message.

Status Indicator

Status

Description

Recommended Action

OFF

No power applied to device

Apply power to device.

Solid green

Device operating normally

None.

Flashing red/OFF

Recoverable fault
- FLEX I/O module bad
- Incorrect FLEX I/O module installed
- External flash checksum error
- Node address changed since power up

Cycle power to device.
Verify the FLEX I/O modules installed.
Verify the FlexBus connectors and communication.
Verify the confiruguration.
If condition persists, replace device.

Solid red

Unrecoverable fault
- Checksum error in program flash
- 3.3V power supply error
- External flash write error

Replace device.

PROFIBUS Indicator

Status

Description

Recommended Action

OFF

No power or no communication
No cyclic communication active, WDT timeout

Apply power to device.
Establish PROFIBUS communication.

Solid green

Data is being transmitted and received

None.

Flashing red/OFF

Recoverable fault
- Invalid Send Parameter data
- Invalid Check Configuration data

Verify that device is properly installed, and reinstall as
needed.

Solid red

Unrecoverable fault
- Unable to communicate

Replace device.

Read DP – Slave Diagnostics Information Message

Ext_Diag_Data field (Length 9 bytes)

Octet

Description

7

Device Related diagnistic header byte (05h)

8

Revision – Minor

9

Revision – Major

10

Adapter Status
Bit 0 – Node Addres Changed
Bits 1…7 – Reserved

11

Node Address switch setting

12

Identifier Related diagnostic header byte (44h)

13…15

Identifier diagnostic bits

(1)

(1)

One identifier bit for each logical module (adapter and each slot use two identifier
bits). The bits set indicate a module fault.