106 Device Data Base (GSD) File

Create Standard and Teaching GSD Files

To start, you need to have a standard GSD file and a teaching GSD file. Follow
these steps.

1. Download the current GSD file from the following website:

http://www.rockwellautomation.com/rockwellautomation/support/net
works/gsd.page

.

2. Using the downloaded file, create a standard GSD file. You can rename this

file copy as *_standard.gsd.

3. In the standard GSD file, you need to create entries for your new I/O

module in the following formats:
– Auto
– Condensed
– Full

4. Create an Auto format entry for your module following the format

shown below.

For example, you have a 1794-OV16P module.

Standard Auto Format Entry

IMPORTANT

The following examples in the next steps illustrate the format for
standard GSD entries.

For detailed descriptions of parameters in the standard GSD file, refer
to the GSD File Specification for Profibus.

TIP

You can refer to existing Auto format entries in the GSD file as
template. See the User Manual for your I/O module to help you
specify the number of input and output words and other
parameters required in the GSD file.

Hex

Number of
Input Words

00

0 Input words

50

1 Input words

51

2 Input words

52

3 Input words

53

4 Input words

...

...

Hex

Number of
Output Words

00

0 Output words

60

1 Output words

61

2 Output words

62

3 Output words

63

4 Output words

...

...

Comment

End every entry with string
EndModule.

Specify name or catalog number
of your module and the format
type. String inside quotation
marks appear in the
Configuration tool.

Assign a unique integer
for your entry.

; Flex I/O module 1794-OV16P/A, (default config= 0 word in, 1 word out)
Module = "1794-OV16P/A / Auto Format" 0x00, 0x60
219
EndModule