Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 46

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

34 Communicate With Your Module

1794-IT8 Word/Bit Description

Word

Dec. Bits
(Octal Bits)

Description

Write Word 0

00…01

Module Data Type

Bit

01

00

Definition

0

0

°C (default)

0

1

°F

1

0

Bipolar counts scaled between -32768…32767

1

1

Unipolar counts scaled between 0…65535

02

Fixed Filter Enable – When this bit is set (1), a software digital filter is enabled. This filter settles to 100%
of a Full Scale step input in 60 scans.

03…05

Notch Frequency

Bit

05

04

03

0

0

0

10 Hz (default)

0

0

1

25 Hz

0

1

0

50 Hz

0

1

1

60 Hz

1

0

0

100 Hz

1

0

1

250 Hz

1

1

0

500 Hz

1

1

1

1000 Hz

06

Gain Offset Calibration – This bit is set during gain calibration/ reset during offset calibration.

07

Calibration Clock – This bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to
initiate calibration.

08…15 (10…17)

Calibration Mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0
corresponds to channel 0, bit 1 to channel 1, and so on.

Write Word 1

00…03

Channel 0 Thermocouple Type

Bit

03

02

01

00

Thermocouple Type – Range

0

0

0

0

Millivolts (default)

0

0

0

1

B 300...1800 °C (572...3272 °F)

0

0

1

0

E -270...1000 °C (-454...1835 °F)

0

0

1

1

J -210...1200 °C (-346...2192 °F)

0

1

0

0

K -71...1372 °C (-95...2502 °F)

0

1

0

1

R -50...1768 °C (-58...3214 °F)

0

1

1

0

S -50...1768 °C (-58...3214 °F)

0

1

1

1

T -73...400 °C (-99...752 °F)

1

0

0

0

C 0...2315 °C (32...4199 °F)

1

0

0

1

N -270...1300 °C (-450...2372 °F)

Advertising