110 Device Data Base (GSD) File

Byte 4

The start address of digital input in bits.

For digital input modules, the start address (in bits) of input
(RTD 1), based on

Example RTD I/O Profile for Sample Non-EDT

Module on page 109

, is 16 bits (RTD0), that is, 0x10.

For analog input modules and non-input modules, this byte is 0x00.

Byte 5

The length of digital inputs in bits.

For digital input modules, the length of digital inputs, based on

Example RTD I/O Profile for Sample Non-EDT Module on page 109

,

is 0x80(I:0 to I:7).

For analog input modules and non-input modules, this byte is 0x00.

Byte 6

The start address of analog input in bits.

For analog input modules, the start address (in bits) of input
(RTD 1), based on

Example RTD I/O Profile for Sample Non-EDT

Module on page 109

, is 16 bits(RTD0), that is, 0x10.

For digital input modules and non-input modules, this byte is 0x00.

Byte 7

The length of analog inputs in bits.

For analog input modules, the length of analog inputs, based on

Example RTD I/O Profile for Sample Non-EDT Module on page 109

,

is 0x80(I:0 to I:7).

For digital input modules and non-input modules, this byte is 0x00.

Byte 8

The start address of Status information in bits.

Based on

Example RTD I/O Profile for Sample Non-EDT Module on

page 109

, the start address (in bits) of Status Information (RTD 9) is

16(RTD 0) + 128(RTD 1…RTD 8) = 144 bits, that is, 0x90.

If there is no Status Information byte in above I/O profile table then
this byte is 0x00.

Byte 9

The length of Status information in bits.

Based on

Example RTD I/O Profile for Sample Non-EDT Module on

page 109

, the length (in bits) is

32(2 words, S0 .. S1), that is, 0x20.

If there is no Status Information byte in the I/O profile table then
this byte is 0x00.

Byte 10

The start address of digital output in bits.

For digital output modules, the start address (in bits) of output
(RTD 11) based on

Example RTD I/O Profile for Sample Non-EDT

Module on page 109

, is 16(RTD 0) + 128 (RTD 1…RTD 8) + 32(RTD

9…RTD 10) = 176 bits, that is, 0xB0.

For analog output modules and non-output modules, this byte is
0x00.

Byte 11

The length of digital output in bits.

For digital input modules, the length of digital output, based on

Example RTD I/O Profile for Sample Non-EDT Module on page 109

,

is 0x10(O:0).

For analog input modules and non-output modules, this byte
is 0x00.

Byte 12

The start address of analog output in bits.

For analog output modules, the start address (in bits) of output
(RTD 11) based on

Example RTD I/O Profile for Sample Non-EDT

Module on page 109

, is 16(RTD 0) + 128 (RTD 1…RTD 8) + 32(RTD

9…RTD 10) = 176 bits, that is, 0xB0.

For digital output modules and non-output modules, this byte is
0x00.

Byte 13

The length of analog output in bits.

For analog output modules, the length of analog output based on

Example RTD I/O Profile for Sample Non-EDT Module on page 109

,

is 0x10(O:0).

For digital input modules and non-output modules, this byte
is 0x00.

Ext_User_Prm_Data_Const(0) Byte Description and Examples for Non-EDT Modules