Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual

Page 30

Advertising
background image

Publication 1794-UM064B-EN-P - May 2014

18 Communicate With Your Module

1794-IA8 – 8-point Discrete Input Module Image Table Mapping

0

1

1

Filter Time 3

2 ms

1

0

0

Filter Time 4

4 ms

1

0

1

Filter Time 5

8 ms

1

1

0

Filter Time 6

16 ms

1

1

1

Filter Time 7

32 ms

1794-IB10XOB6 Input Filter Times

Description

Selected
Filter Time

02

01

00

Filter Time for Inputs 00…07

1794-IA8 Memory Map

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read/Write Words

Not used

D7

D6

D5

D4

D3

D2

D1

D0

Read Word 0

Not used

Read Word 1

Not used

FT 00…07

Not used

Write Word 0

Where:

D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1,and so on)
FT = Input Filter Time (FT 00…07 corresponds to inputs 0…7)

Filter

Time

1138

1794-IA8 Input Filter Times

Bits

Description

Maximum Filter Time

02

01

00

Filter Time for Inputs 00…15 (00…17)

Off to On

On to Off

0

0

0

Filter Time 0 (default)

8.6 ms

26.6 ms

0

0

1

Filter Time 1

9 ms

27 ms

0

1

0

Filter Time 2

10 ms

28 ms

0

1

1

Filter Time 3

12 ms

30 ms

1

0

0

Filter Time 4

17 ms

35 ms

1

0

1

Filter Time 5

26 ms

44 ms

1

1

0

Filter Time 6

43 ms

61 ms

1

1

1

Filter Time 7

78 ms

96 ms

Advertising