Appendix D Configure a Series A Kinetix 3 Drive
8. In the personal computer Communication Setup dialog box, configure the serial port, as follows:
– Baud Rate: 57600
– Format: 8 Data Bits, No Parity
9. Click OK.
10. From the Tools menu, choose Rescan.
The drive attaches at Node 1 and appears in the On-Line Drives tree when the scan is complete.
If
Then
Communication was established.
You are prompted to use a wizard to set up the Kinetix 3 drive. You are not required to use it, but it simplifies configuration.
Communication was not established
There is an error in the communication setup, the drivers, or the wiring