Rockwell Automation Publication CC-QS033A-EN-P - February 2014

91

Configure a Series A Kinetix 3 Drive Appendix D

Configure Your Drive with Ultraware Software

Follow these steps to configure your Kinetix 3 drive for the building block.

1. Factory reset the drive to provide a consistent starting point.

a. From the top-level branch, double-click Drive.

b. From the right pane, click Reset to Factory Settings.
c. Click Yes.

2. Configure the Follower mode.

a. Expand Mode Configuration.
b. Double-click Follower branch.

The parameters are shown in the right pane.

c. Set the Command Type to Step/Direction. Positive Logic.

d. Set the 1st Gear Ratio Change to Always Enable.
e. Set the 1st Gear Ratio to 1:128.