A.5 Alarm Monitoring

A -7

A.5 Alarm Monitoring

Table A.5. Alarms

Name

# Register

Details

Alarm

IL jj 22

Servo Controller alarms are monitored using bit information.

b0: SVERR

Servopack Error

Servopack alarm detected. (For alarm details see IWjj24.)

b1: OTF

Positive Overtravel

Positive overtravel detected in the Servopack. (The P-OT signal is ON.)

b2: OTR

Negative Overtravel

Negative overtravel detected in the Servopack. (The N-OT signal is ON.)

b3: SOTF

Positive Software Limit

Movement detected beyond the positive software limit range.

b4: SOTR

Negative Software Limit

Movement detected beyond the negative software limit range.

b5: SVOFF

Servo Power OFF

A motion command was issued while the Servo power was OFF.

b6: TIMEOVER

Positioning Time Over

After completion of distribution, positioning was not completed within the
time specified in OWjj34 (Positioning Check Time).

b7: DISTOVER

Positioning Distance Over

Movement attempted which exceeds the positioning distance limit.

b8: FILTYPERR

Filter Type Error

Attempt was made to change the filter type before distribution was com-
pleted.

b9: FILTYMERR

Filter Time Error

Attempt was made to change the filter time before distribution was com-
pleted.

b10: MODERR

Control Mode Error

Position Control Mode motion commands were issued in a mode other than
Position Control Mode.

b11: SET_NRDY

Zero Point Not Set

The zero point has not been set.