background image

Reference

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 100 of 159

ProSoft Technology, Inc.

August 6, 2010

The events can be returned for Class 1 or Class 2 requests according to the data

type as follows:

Data Type

Class Request

M_SP_NA

Class 1

M_DP_NA

Class 1

M_ST_NA

Class 1

M_BO_NA

Class 1

M_ME_NA

Class 2

M_ME_NB

Class 2

M_ME_NC

Class 2

M_IT_NA

Class 1


Note:
In response to a Class 2 poll the gateway may respond with Class 1 data when there is no

Class 2 data available. So eventually the events for M_SP_NA, M_DP_NA and M_ST_NA points

may also be sent during a Class 2 response.

Deadbands
The Monitored Measured points (M_ME_NA and M_ME_NB) will generate

events only if the data value changes an amount greater than or equal to the

configured deadband value.
For example, if the following point is configured:

Then, if the current value for this point is 130, it would generate events only if:

NEW VALUE is less than or equal to 30

OR

NEW VALUE is greater than or equal to 230.

Each monitored measured point can have its own deadband value assigned to it

in the configuration file or by using the PCB configuration options.