From address, To address, Register count – ProSoft Technology 5201-MNET-101S User Manual

Page 18: Swap code

Advertising
background image

Start Here

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 18 of 159

ProSoft Technology, Inc.

August 6, 2010

From Address
0 to highest Status Data address
This field specifies the beginning internal database register address for the copy

operation. This address can be any valid address in the User Data Area or the

Status Data Area of the gateway.

To Address
0 to 3999
This parameter specifies the beginning destination register address for the copy

operation. This address must always be within the User Data registers area.

Take care to specify a destination address that will not overwrite data that has

been stored in memory by one of the communication protocols running on the

gateway.

Register Count
1 to 100
This parameter specifies the number of registers to copy.

Swap Code
N

O

C

HANGE

,

W

ORD

S

WAP

,

W

ORD AND

B

YTE

S

WAP

,

B

YTE

S

WAP

You may need to swap the order of the bytes in the registers during the copy

process in order to change the alignment of bytes between dissimilar protocols.

This parameter is helpful when dealing with floating-point or other multi-register

values, as there is no standard method of storage of these data types in slave

devices.

Advertising
This manual is related to the following products: