101S Protocol Configuration

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 36 of 159

ProSoft Technology, Inc.

August 6, 2010

2.1.29 Response Timeout

0 to 65535

milliseconds

This parameter specifies the minimum number of milliseconds to wait for a

response to a primary message. Do not set this parameter too small or timeout

conditions may prevent successful data transmission. If the timeout is

recognized, the message will be retransmitted up to the number of times

specified in the Retry Count parameter. This parameter is only used in balance

mode.

2.1.30 Baud Rate

300, 600, 1200, 2400, 4800, 9600, 19200, or 38400
This parameter specifies the baud rate for the primary port on the gateway. Baud

rates from 300 to 38400 are supported on the gateway.

2.1.31 Parity

None, Odd, Even
Parity is a simple error checking algorithm used in serial communication. This

parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.

2.1.32 RTS On

0 to 65535

milliseconds

This parameter sets the number of milliseconds to delay after Ready To Send

(RTS) is asserted before data will be transmitted.

2.1.33 RTS Off

0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after the last byte of

data is sent before the RTS modem signal will be set low.

2.1.34 Minimum Delay

0 to 65535

milliseconds

This parameter defines the minimum number of milliseconds to wait before a

response is sent from the unit.