ProSoft Technology 5201-MNET-101S User Manual

Page 32

Advertising
background image

101S Protocol Configuration

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 32 of 159

ProSoft Technology, Inc.

August 6, 2010

The gateway will automatically set ON (set to one) the IV Bits of all IEC database

Monitor Points (M_xx_xx point) that have been configured to use invalid bit

monitoring. This means that all IEC database Monitor Points configured with IV

Bit addresses greater than zero (0) will have their IV Bit addresses in the

gateway database set to a value of one (1) by the gateway firmware in a timed,

periodic cycle, based on the number of seconds entered in Cyclic Set IV Time.
The IV Bits are checked at the interval specified by the IV Check Delay Time

parameter. At the end of each check delay interval, if an IV Bit for any IEC

database point is ON, an IV Bit Check Fail accumulator for that point will be

incremented. If the value in any IV Bit Check Fail accumulator becomes equal to

the value of the IV Fail Count parameter, the gateway will consider the data value

of that point invalid and will report the invalid status of that point to the Master

along with the data value.
If the IV Bit is cleared (reset, set OFF, set to zero) before the IV Bit Check Fail

accumulator value becomes equal to the value of the IV Fail Count parameter,

the IV Bit Check Fail accumulator will be reset to 0. The gateway will consider the

data value of that point valid and will report the valid status of that point to the

Master along with data value.
To properly use data validity checking with a ProLinx Gateway, the application

that communicates to the gateway through the other gateway protocol (Modbus,

EtherNet/IP, etc.) must be programmed to provide data validity information, as

well as the actual data to be transferred. This other application must write bit

values of zero (0) or one (1) to the proper gateway database addresses along

with the data for each IEC database point.
This means the other protocol application will be responsible for clearing the IV

Bits for data points which contain valid data at a time interval less than the

amount of time required to accumulate the required number of IV Bit Check

failures. If the other protocol application does not clear the IV Bits, then those

IEC database monitor point values will be reported to the Master as invalid.

NOTE: If one or more of the Cyclic Set IV Time, the IV Check Delay Time, or the IV Fail Count

parameters are set to zero, the data validity checking feature will be disabled for all points in the

IEC database and the data reported to the remote Master will always be reported as valid data. If

you wish to have actual data validity information relayed to the Master, be sure the Cyclic Set IV

Time, the IV Check Delay Time, and the IV Fail Count parameters are set to non-zero values and

be sure the application has been programmed to properly manipulate the IV Bit addresses in the

gateway database. Once data validity checking has been enabled, you can still turn off validity

checking on a point-by-point basis by setting the IV Bit Address to zero (0) for any point you wish to

exclude from data validity checking and reporting.


For more information on the data validity features of this protocol implementation,

refer to Invalid Bit Monitoring.

Advertising
This manual is related to the following products: