M_me_na – ProSoft Technology 5201-MNET-101S User Manual

Page 103

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 103 of 159

August 6, 2010

And if the parameter offsets are configured as follows:

It would imply that the parameter points would be configured as follows:

M_ME_NA

Monitored Measured Normalized Point

Associated Parameter Point

400

2400

401

2401

402

2402

403

2403

404

2404

So, in order to send change the deadband for the M_ME_NA point 400, the

Master would send a command type 110 to point 2400: