IEC-101 Slave ♦ ProLinx Communication Gateway

IEC 60870-5-101 Slave Interoperability Statement

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 131 of 159

August 6, 2010

6.4 Link Layer

(Network-specific parameter)
Frame format FT 1.2, single character 1 and the fixed time out interval are used

exclusively in this companion standard.

Link transmission procedure

Address field of link

Balanced transmission

Not present (balanced transmission only)

Unbalanced transmission

One octet

Two octets

Structured

Frame length

Unstructured

25 to 252 Maximum length L (number of octets)

6.5 Application Layer

6.5.1 Transmission Mode for Application Data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,

is used exclusively in this companion standard.

6.5.2 Common Address of ASDU - 101S

(System-specific parameter)

One octet  Two octets

6.5.3 Information Object Address

(System-specific parameter)

One octet  Structured

Two octets

Unstructured

Three octets

6.5.4 Cause of Transmission

(System-specific parameter)

One octet  Two octets (with originator address)

6.5.5 Length of APDU - 101S

(System-specific parameter, specify the maximum length of the APDU per

system)
The maximum length of the APDU in this protocol implementation is 252

(default). The maximum length may be reduced by the system.
The maximum length of APDU per system is 255.