Example 2 - command request with response only, Command request block, Command response block – ProSoft Technology 5201-MNET-101S User Manual
Page 119

IEC-101 Slave ♦ ProLinx Communication Gateway
Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 119 of 159
August 6, 2010
Example 2 - Command Request with Response Only
For this example, the remote node is requesting the event buffer sizes from the
ProLinx gateway. This is an example of a request that requires a response back
from the gateway:
The following block can be used for the first request.
Command Request Block
Word Offset Database
Address
Value
Description
0
3000
0
Block ID1 - Command Request Without Response
Move a value of 0 or any other value out of the 100
to 101 and 200 to 201 range, because no request
without response is performed
1
3001
202
Block ID2 - Command Request With Response.
2 to 98
3002 to 3098 Not Used
Not Used
99
3099
0
Block ID1 - Command Request Without Response
Move a value of 0 or any other value out of the 100
to 101 and 200 to 201 range, because no request
without response is performed
Command Response Block
Word
Offset
Database
Address
Value
Description
0
3100
202
Block ID2 - Command Request With Response.
1
3101
0
Block ID1 - Command Request Without Response
2 to 8
3102 to 3108 Event Buffers Event Buffers
99
3199
202
Block ID2 - Command Request With Response.
In order to send another command request to pass another event, use the
following format: