IEC 60870-5-101 Slave Interoperability Statement

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 136 of 159

ProSoft Technology, Inc.

August 6, 2010

Type Identification

Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13 20

to

36

37

to

41

44 45 46 47

<59>

C_DC_TA_1

X X X X X

X X X X

<60>

C_RC_TA_1

X X X X X

X X X X

<61>

C_SE_TA_1

X X X X X

X X X X

<62>

C_SE_TB_1

X X X X X

X X X X

<63>

C_SE_TC_1

X X X X X

X X X X

<64>

C_BO_TA_1

X X

X

X X X X

<70>

M_EI_NA_1

X

<100> C_IC_NA_1

X X X X X

X X X X

<101> C_CI_NA_1

X X

X

X X X X

<102> C_RD_NA_1 X

X X X X

<103> C_CS_NA_1

X X

X X X X

<105> C_RP_NA_1

X X

X X X X

<107> C_TS_TA_1

X X

X X X X

<110> P_ME_NA_1

X X

X X X X

<111> P_ME_NB_1

X X

X X X X

<112> P_ME_NC_1

X X

X X X X

<113> P_AC_NA_1

<120> F_FR_NA_1

<121> F_SR_NA_1

<122> F_SC_NA_1

<123> F_LS_NA_1

<124> F_AF_NA_1

<125> F_SG_NA_1

<126> F_DR_TA_1

<127> F_SC_NB_1