ProSoft Technology 5201-MNET-101S User Manual

Page 101

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 101 of 159

August 6, 2010

A network Master may also dynamically change the deadband for each

monitored point. The Master may send one of the following commands:

Type

Command

110

Parameter of Measured Normalized Data (M_ME_NA)

111

Parameter of Measured Scaled Data (M_ME_NB)

112

Parameter of Measured Short Floating Point (M_ME_NC)

The protocol specification explains that the qualifier value for these commands

should be configured as:

Bits

Value

Description


1 to 6

0

Not Used

1

Threshold Value (Deadband)

2

Smoothing Factor (filter time constant) - Not Supported

3

Low Limit Transmission of Measured Value

4

High Limit Transmission of Measured Value

5..31

Reserved

7

0

No Change

1

Change

8

0

Operation

1

Not in Operation

The gateway calculates the Low Limit and High Limit values using the formula

below (so these values cannot be changed dynamically)
Low Limit = (LAST REPORTED VALUE) - Deadband
High Limit = (LAST REPORTED VALUE) + Deadband
These commands must be sent to a specific Information Object Address. The

gateway associates each monitor measured point with a parameter point through

the following configuration parameters: