Reference

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 82 of 159

ProSoft Technology, Inc.

August 6, 2010

Monitor Data Transfer
In unbalanced mode, the polling procedure is initiated from the Master unit

through Class 1 and Class 2 requests. In general, ASDUs containing

periodic(cyclic) causes of transmission are typically assigned to be transmitted in

response to Class 2 requests from the Master. All ASDUs containing time-tagged

or spontaneous causes of transmission are typically assigned to be transmitted in

response to Class 1 requests. Other ASDUs with other causes of transmission of

low priority, such as background scans, may also be assigned to be transmitted

in response to Class 2 requests.
Typically, you should properly configure the group code (page 50) for each

monitor point to define how the Master will poll for the point.
The gateway will periodically send all points configured for periodic/cyclic poll

(0x80000000) at every x milliseconds, where x is configured with the Cyclic Data

Transmission parameter: